|
The role of the maintenance bypass has been around since Uninterruptible Power systems were
first introduced. The need for this package became obvious when a complete shutdown of the
UPS was required, but the user could not tolerate an interruption (down time) of the load.
The solution was to make available a second discrete power feed that the load could be
switched to without interruption. This allowed for total isolation of the load from the UPS,
freeing the UPS System for complete service or maintenance. This remains the fundamental
role of the Maintenance Bypass System
The only stumbling block to adding this enhancement to the power design was the safety aspect
both to the operator and the system. The first inclination was, and still is, to simply
install two breakers in the critical switchboard, one to isolate the UPS from the load and a
second to supply the load with utility power. This is precisely what the maintenance bypass
system does, but the hazards are numerous if there are no controls in place to prevent the
improper operation of these two very critical breakers.
The hazard that is most often recognized initially is the accidental closing of the utility
breaker (MBP breaker) while the UPS is still online. The results of this act on the UPS can
be quite disastrous and also includes the potential for an interruption of the power load as
well. If there is no power available at the time from the utility, this scenario now poses a
potential hazard to the Utility (Electrical Authority) in the form of a lethal back-feed to
the utility from the UPS.
A second concern that the Electrical Authority commonly raises, is that even if operated in
the proper sequence with the UPS on internal bypass, there still exists the potential to
back-feed the lines. Especially if the two breakers are allowed to remain closed for an
extended period. The potential for continuous reverse feed presents a serious electrical
hazard to the Utility's electrical service personnel. A second concern raised by the
Electrical Authority is that in many instances the breaker coordination is affected,
jeopardizing the protection of the critical feeder due to two breaker paths feeding one line.
In some instances leaving both breakers closed will feed twice the rated current to the
cables.
These concerns help illustrate why Utility inspectors became increasingly less tolerant of
maintenance bypass systems while at the same time consumers became more demanding for the
use of them. It became such an issue with the Utility that at one time some inspectors would
not pass a UPS installation with a maintenance bypass system unless it was mechanically
interlocked ("break before make"). This met the Utility's concerns but negates the true
purpose of the system. This scenario led to the development of the Maintenance Bypass System
supplied by Critical Distribution.
This package is a self contained Maintenance Bypass System that is built with CSA and Hydro
approval using an electrical interlock that works on a two wire fail-safe circuit. This
"single pair" of wires require a dry contact closure within the UPS System ("UPS on Bypass")
for the transfer enabled condition. Without this contact closed, the system prevents the
closing of the alternate breaker. This allows the Maintenance Bypass System to address all
of the above concerns.
|